Flush Mount Mantel Installation (Figure 11)
The fireplace must extend 3/4" beyond finished wall surface when
using a flush mount mantel. Refer to Figure 11 to locate nailing
flanges on fireplace sides. Mark and drill two (2) 1/8" holes into
fireplace side to mount each nailing flange. Use eight (8) 1/2" hex-
head screws supplied in hardware package to attach nailing flanges
to fireplace sides.
NAIL OR OTHER SUITABLE FASTENER
Attention: When fireplace is installed in optional full cabinet mantel
or corner mantel the (4) four nailing flanges shown in Figure 11 will
not be installed on the side of outer casing. The fireplace will be
attached to the full cabinet mantel or corner mantel with the (2) two
nailing flanges located on the top of the outer casing assembly.
Framing (Figure 12)
Fireplace framing can be built before or after the fireplace is set in
place. Framing should be positioned to accommodate wall covering
and fireplace facing material. The fireplace framing should be
constructed of 2 x 4 lumber or heavier. The framing headers may
rest on the fireplace standoffs. Refer to Figure 12 for minimum
framing dimensions.
MEASURE FIREpLACE DIMENSIONS AND vERIFY FRAMING
METHODS, AND WALL COvERING DETAILS BEFORE
FRAMING CONSTRUCTION BEGINS.
Framing dimension "A" includes a three inch clearance
for standoffs on fireplace. After installing fireplace into
framing, the finished non-combustible wall surface must
cover the three inch opening above the fireplace.
26927-8-0611
INSTALLATION (continued)
Figure 11
CAUTION
NOTICE: For finishing to top of fireplace, refer to Figure 12.
"A"
"B"
"C"
Attention: Add 3-3/4" to "A" dimensions when using a flush mantel
base.
Attention: If a base or mantel is not used and the appliance is
installed directly on carpeting, tile or other combustible material other
than wood flooring, it shall be installed on a metal or wood panel
extending the full width and depth of the appliance. The vertical
dimension in Figure 12 must be adjusted when a metal or wood
panel is placed beneath the appliance.
Finishing (Figures 13 and 14)
Finish the walls with the material of your choice. Figure 3 on page 8
shows the minimum vertical and corresponding maximum horizontal
dimensions of mantels or other combustible projections above the
top front edge of the fireplace.
Only non-combustible materials may be used to cover the black
fireplace front.
When finishing the fireplace never obstruct or modify the
air inlet/outlet louvers in any manner. provide adequate
clearances around air openings into the combustion
chamber.
If the joints between the finished wall and the fireplace surround
(top and sides) are sealed, a 300°F minimum sealant material
must be used. These joints are not required to be sealed. Only
non-combustible material (using 300°F minimum adhesive if
needed), can be applied as facing to the fireplace surround.
DVP36
37 7/8"
40 3/8"
19 7/8"
Figure 12
WARNING
CAUTION
Page 13