Determining the boiler set-point

Start-up and Maintenance
Outside temperature
Legend
Start-up and Maintenance
A Selector dial "tr" setting: 1
B Selector dial "tr" setting: 2
C Selector dial "tr" setting: 3
D Selector dial "tr" setting: 4
E Factory default
F Selector dial "tr" setting: 5
G Selector dial "tr" setting: 6
Fig. 72
Factory default
Troubleshooting
Room dependent control:
Outdoor temperature sensor not
connected
With no outdoor sensor installed, the
"tr" dial will provide a constant
temperature set-point for the boiler
based on the dial position selected.
Setting the dial between 1 and 6 will
provide a set-point value of 81º F to
178º F / 27º C to 81º C respectively.
The dot between 4 and 5 represents
the factory default set-point value of
140º F / 60º C.
Weather dependent control:
Outdoor temperature sensor
connected
With the outdoor sensor connected,
the boiler will automatically recognize
the sensor and switch the set-
point dial operation from constant
temperature calculated to outdoor
reset calculated.
Adjusting the "tr" dial will select
the heating curve corresponding with
the heating curve chart. The set-point
will be calculated from the design
boiler water temperature associated
with the heating curve selected, and
reset from the actual outdoor air
temperature. Setting the dial between
1 and 6 will select the corresponding
curve from the chart. The dot
between 4 and 5 is the factory
default curve.
Note:
Both the room dependent control and
the outdoor reset control strategies
require a closed contact at terminals
RT to generate a call for heat to the
boiler.
Setting the dial to "0" places the
boiler in freeze protection mode
regardless of the control option
selected or the contact position at RT.