Gas piping pressure test

When performing the gas piping pressure test, ensure the following
requirements are met.
WARNING
Never check for gas leaks with an
open flame.
WARNING
Exposing boiler gas pressure
regulator and gas valve to extreme
pressures renders warranty null and
void.
IMPORTANT
½ psig = 14 "w.c.
Boiler Connections
1. Isolate the boiler from the gas
supply piping system using the
individual manual shutoff valve
during pressure tests equal to or
less than ½ psig/14 "w.c.
2. The boiler and its individual
shutoff valve must be
disconnected from the gas supply
piping system during any pressure
testing of that system at test
pressures in excess of
½ psig/14 "w.c.
3. Perform leak test.
Use approved liquid spray
solution for bubble test.
Ensure that no liquid is sprayed
on any electrical components,
wires or connectors. Do not
allow leak detection fluid
to contact gas valve regulator or
regulator vent opening.
4. Correct any and all deficiencies.
5. Remove air from gas line.
21