Boiler installation
7.7

Gas supply connection

7.7.1 Installing gas feed
For the gas pipe diameter required for the installation
please see Tab. 4 and Tab. 5. Make sure that the pipe
fitting has the correct thread size.
Make sure that a sediment trap is installed at the inlet for
the gas supply pipe to the boiler. A hand stop valve must
be installed outside the boiler jacket if required by the
local code. We recommend installing a hand stop valve
in the main gas pipe to the boiler. The gas pipes must be
fastened outside the boiler.
USER NOTE
The gas supply pipe is designed for a gas
connection on the right side.
If the gas feed is from the left, the gas
connection pipe must be completely
unscrewed, turned 180° and installed
again.
Check the connection for leaks.
Please support extenion gas piping to
relieve stress on gas train.
The local codes must be observed during installation of
the gas connection, otherwise the regulations of the
National Fuel Gas Code, ANSI Z 223.1.
DANGER OF EXPLOSION
Leakage from the gas pipes and gas
connections may cause an explosion.
WARNING!
Use soap solution to find leaks.
SYSTEM DAMAGE
due to short-circuit.
Cover the hazardous locations before
CAUTION!
checking for leaks.
Do not spray the leak solution on wiring
openings, plugs or electrical
connections. Do not allow the solution
to drip on these locations.
Length
Gas pipe supply volume in cubic feet of gas
of pipe
in feet
1"
1¼"
10
520
1060
20
350
730
30
285
590
40
245
500
50
215
440
75
175
360
100
160
305
150
120
250
Tab. 4
Gas pipe supply volume
1
Maximum gas supply volume in cubic feet per hour, based on a
specific gas weight of 0.60 and a gas pressure of 0.5 psi or less
and a pressure gradient corresponding to a water column of
0.3 inches.
20
1
per hour
1½"
2"
2½"
1600
3050
4800
1100
2100
3300
890
1650
2700
760
1450
2300
670
1270
2000
545
1020
1650
480
870
1400
380
710
1130
Installation and maintenance instructions Logano G334 X gas-fired boiler • Issue 09/2005
4
Fig. 18 Pipe connection to gas valves – back view
1 Gas feed
2 Main gas shut-off valve
3 Sediment trap
4 Retaining screws at the gas supply line
We reserve the right to make any changes due to technical modifications.