Gas-fired boiler propane conversion kit instructions

Advertisement

6304 2381 – 09/2005 US/CA
Propane Conversion Kit
Instructions
Logano G334 X gas-fired boiler
This conversion kit and the accompanying instructions are for conversion of
G334 X gas-fired boilers from natural gas to propane.
G334 X-73
G334 X-92
301 MBtu/hr
378 MBtu/hr
WARNING!
This conversion kit is intended for use by a
qualified service company only as
specified by the manufacturer's
instructions and the current applicable
rules and regulations of the local
authorities and the regulations of
NFPA54, CAN/CGA B149.1 and 2,
Installation Code, must also be observed.
If these instructions are not followed
exactly, a fire, explosion or release of
carbon monoxide may occur with serious
property damage or loss of life and serious
injury. The heating contractor is liable for
correct conversion of the heating system
with this conversion kit.
CAUTION!
Before converting the heating system to a
different type of gas the gas line must first
be shut off and then the power to the
heating system must be disconnected.
Note: Please keep these instructions for future reference.
Please read carefully before conversion
Required Input Rates
G334 X-116
476 MBtu/hr
For heating engineers
G334 X-132
541 MBtu/hr

Advertisement

Table of Contents
loading

Summary of Contents for Buderus Logano G334 X

  • Page 1 6304 2381 – 09/2005 US/CA For heating engineers Propane Conversion Kit Instructions Logano G334 X gas-fired boiler This conversion kit and the accompanying instructions are for conversion of G334 X gas-fired boilers from natural gas to propane. Required Input Rates...
  • Page 2: Table Of Contents

    ....... 11 We reserve the right to make any changes due to technical modifications. Instructions for conversion kit for Logano G334 X gas-fired boiler • Issue 09/2005...
  • Page 3: Safety

    4. unit label (to be filled out and attached to the unit) 5. Technical documents We reserve the right to make any changes due to technical modifications. Instructions for conversion kit for Logano G334 X gas-fired boiler • Issue 09/2005...
  • Page 4: Conversion To Propane

    Page 9. If there is no sign of a gas odor, continue with the next step. Fig. 2 Gas valve We reserve the right to make any changes due to technical modifications. Instructions for conversion kit for Logano G334 X gas-fired boiler • Issue 09/2005...
  • Page 5 3 Stainless steel spiral spring 4 Gas valve 5 Yellow label We reserve the right to make any changes due to technical modifications. Instructions for conversion kit for Logano G334 X gas-fired boiler • Issue 09/2005...
  • Page 6 Removing the gas burner 8501 and 12000 feet above sea level. 1 Fixing nuts 2 Threaded studs We reserve the right to make any changes due to technical modifications. Instructions for conversion kit for Logano G334 X gas-fired boiler • Issue 09/2005...
  • Page 7 We reserve the right to make any changes due to technical modifications. Instructions for conversion kit for Logano G334 X gas-fired boiler • Issue 09/2005...
  • Page 8 2 Screw plug for gas supply pressure measuring port page. 3 Screw plug for manifold measuring port We reserve the right to make any changes due to technical modifications. Instructions for conversion kit for Logano G334 X gas-fired boiler • Issue 09/2005...
  • Page 9: Start-Up Instructions

    We reserve the right to make any changes due to technical modifications. Instructions for conversion kit for Logano G334 X gas-fired boiler • Issue 09/2005...
  • Page 10: Making Boiler Ready For Operation

    Fig. 8 Switching on heating system (with aquastat) 1 ON/OFF switch (main switch) We reserve the right to make any changes due to technical modifications. Instructions for conversion kit for Logano G334 X gas-fired boiler • Issue 09/2005...
  • Page 11: Then Carry Out Start-Up Procedures

    7. Look at the igniter through the sight glass in the burner housing. Fig. 10 Front view 1 Sight glass We reserve the right to make any changes due to technical modifications. Instructions for conversion kit for Logano G334 X gas-fired boiler • Issue 09/2005...
  • Page 12 ( Fig. 11 page 12) into the gas valve again. We reserve the right to make any changes due to technical modifications. Instructions for conversion kit for Logano G334 X gas-fired boiler • Issue 09/2005...
  • Page 13 Disconnect heating system from the power supply and inform the customer service technician or gas company. We reserve the right to make any changes due to technical modifications. Instructions for conversion kit for Logano G334 X gas-fired boiler • Issue 09/2005...
  • Page 14 With the Logamatic 2107 control only 34. Select AUT (automatic mode) with the mode selection switch. We reserve the right to make any changes due to technical modifications. Instructions for conversion kit for Logano G334 X gas-fired boiler • Issue 09/2005...
  • Page 15 Notes We reserve the right to make any changes due to technical modifications. Instructions for conversion kit for Logano G334 X gas-fired boiler • Issue 09/2005...
  • Page 16 Heating Contractor: PRODUCTS MANUFACTURED BY BBT Thermotechnik GmbH 35573 Wetzlar www.buderus.de BBT North America Corporation 50 Wentworth Avenue Londonderry, NH 03053 Tel: 603-552-1100 ● Fax: 603-584-1681 www.buderus.net BBT North America Corporation reserves the right to make changes without notice due to continuing engineering and technological advances.

Table of Contents