Boiler installation
5.4

Fuel gas supply connection

Heed the following points for connecting the fuel supply:
▶ Work on gas components may only be carried out by
qualified and authorized personnel.
▶ Observe the local regulations or else the requirements
the National Fuel Gas Code, ANSI Z 223.1 when
connecting the gas supply. In Canada, the
requirements of CAN/CSA-B.149.1 and 2,
Installation Guidelines, must be observed.
▶ A gas shut-off valve must be installed outside the
boiler casing if required by the local code. We
recommend installing a gas shut-off valve in the main
gas pipe to the boiler.
▶ The gas pipes must be fastened outside the boiler.

5.4.1 Installing gas feed

For details of the required gas pipe diameter, refer to Tab. 7 and Tab. 8
on page 12. Make absolutely sure that the pipe fittings have the correct
thread size.
▶ Make sure that a sediment trap is fitted at the inlet for the gas supply
pipe to the boiler.
The gas feed pipe is designed for a gas connection on the
right side.
For the conversion to left-side gas connection, see
section 5.1.
To prevent strain on the gas valves, extensions of the gas
supply line must be supported.
Gas pipe delivery rate in cubic feet of gas per hour
Length of the pipe in feet
(1 foot = 0.3 m)
1"
10
520
20
350
30
285
40
245
50
215
75
175
100
160
150
120
Table 7 Gas pipe delivery rate
1) Maximum gas pipe delivery rate in cu ft/hr (1 ft
equivalent to a water column of 0.3 inches (7.6 mm).
Iron pipe nominal diameter (in
inches)
1
2
Table 8 Equivalent lengths for pipe fittings
12
1¼ "
1060
730
590
500
440
360
305
250
3
/h = 28.3 l/h) based on a gas specific gravity of 0.60 and a gas pressure of 0.5 psi (34.5 mbar) or less and a pressure drop
Equivalent lengths for pipe fittings in feet (1 foot = 0.3 m)
Type of pipe fitting
90° elbow
T-piece
3
5
4
6
5
7
7
10
8
12
Fig. 11 Gas valve pipe connection
[1]
Gas supply
[2]
Shut-off
[3]
Sediment trap
[4]
Retaining screws at the gas feed line (on site)
1)
3
(1 ft
/h = 28.3 l/h)
1½ "
2"
1600
3050
1100
2100
890
1650
760
1450
670
1270
545
1020
480
870
380
710
Shut-off valve
0.6
0.8
1.0
1.3
1.6
Logano G234X – 6 720 804 886 (2012/08)
2½ "
4800
3300
2700
2300
2000
1650
1400
1130
Gas shut-off valve
1.60
2.15
2.50
3.00
3.50