▶ Cancel the flue gas test; press
Fig. 30 Calling up the flue gas test
7.8.3
Accessing the service level on the RC35 and displaying
monitoring data
▶ Press
+
+
simultaneously to open the SERVICE
MENU menu.
▶ Turn rotary selector
anticlockwise until diagnosis is selected
(marked with
).
▶ Press
to open the SERVICE/DIAGNOSIS menu.
▶ Turn rotary selector
anticlockwise until monitor value is
selected (marked with
SERVICE/DIAGNOSIS
function test
B
monitor value
diagnosis
servicing
▶ Press
to open the DIAGNOSIS/MON. VALUE menu.
▶ Turn rotary selector
anti-clockwise until boiler / burner is
selected (marked with
DIAGNOSIS/MON. VALUE
B
boiler / burner
domestic hot water
heating circuit 1
bus users
to open BOILER / BURNER menu.
▶ Press
The values monitored are displayed as a list; in other words, more
values will appear if the rotary selector is turned.
The current burner output (set/actual) and the flame current can be
checked in these menus.
Logano plus GB402 – 6 720 820 700 (2018/01)
again.
).
).
7.9
Measuring the gas supply pressure and static
pressure
▶ Undo the threaded plug on the test nipple for gas supply pressure
and venting by two turns.
▶ Push the test hose of the pressure gauge (measurement precision
less than 0.1 mbar) onto the pressure test nipple [1].
▶ With the burner operational (full load), check the gas supply pressure
and record the value in the commissioning report
( Chapter 7.18, page 31).
▶ If the gas supply pressure falls outside the values in tab. 12, shut
down the boiler and notify the gas supplier. Commissioning is not
permitted!
The maximum permitted gas static pressure depends on
• the proper function of the gas pressure regulator in the gas
installation in accordance with its product-specific tolerance
specifications for the permitted closing group.
• the product-specific specifications for the boiler in accordance with
the manufacturer's information.
Checking of the gas pressure regulator in the gas installation:
▶ Shut down the burner from full load.
▶ Wait 10-20 seconds and then measure the resulting gas supply
pressure/static pressure at the test nipple for the gas supply
pressure/static pressure.
The gas static pressure determined must not exceed the value, which is
defined by the closing group of the gas pressure regulator.
▶ If it is exceeded, inform the gas supplier about the required
replacement of the gas pressure regulator.
▶ If the gas static pressure is >50 mbar, there must be no
commissioning as specified by the manufacturer.
In the case of a system currently operating, take the boiler out of
operation.
▶ Remove the test hose.
▶ Carefully tighten the threaded plug on the test nipple for gas supply
pressure.
Fig. 31 Testing the gas supply pressure
[1]
Pressure test nipple for testing the gas supply pressure and for
venting
Start up the heating system
7
27