6.2.4 Control I/O

Reference
k Ω
Potentiometer 1-10
Cabling and connections
Terminal
1
+10V
Reference output
ref
2
AI1+
Analogue input, voltage range
0—10V DC.
3
AI1-
I/O Ground
4
AI2+
Analogue input, current range
0—20mA
5
AI2-
/GND
6
+24V
Control voltage output
7
GND
I/O ground
8
DIN1
Start forward (programmable)
9
DIN2
Start reverse (programmable)
10
DIN3
Preset speed selection 1
(programmable)
11
GND
I/O ground
18
AO1+
Output frequency
mA
Analogue output
19
AO1-
A
RS 485
Serial bus
B
RS 485
Serial bus
30
+24V
24V aux. input voltage
21
RO1
22
RO1
23
RO1
Table 6-7. Default I/O configuration.
Terminal
12
+24V
+24 V DC
13
GND
I/O ground
14
Exp DIN1
Preset speed selection 2
(programmable)
15
Exp DIN2
Fault Reset
(programmable)
16
Exp DIN3
Disable PID (PID control
selection)
(Programmable)
25
Exp RO1
Expander Relay output 1 (NO)
RUN
26
Exp RO1
28
TI+
Motor Thermistor input
29
TI-
Table 6-8. Additional inputs in NXL HVAC (available as option for NXL Compact)
Terminal
1
+10V
Reference output
ref
2
AI1+
Analogue input, voltage range
0—10V DC
or
DIN 4
3
AI1-
I/O Ground
4
AI2+
Analogue input, voltage range
0—10V DC or current range
5
AI2-
0—20mA
/GND
6
+ 24 V
Control voltage output
7
GND
I/O ground
Table 6-9. AI1 configuration, when programmed as DIN4
Signal
Voltage for potentiometer, etc.
Voltage input frequency reference
Ground for reference and controls
Current input frequency reference
Voltage for switches, etc. max 0.1 A
Ground for reference and controls
Contact closed = start forward
Contact closed = start reverse
Contact closed = Preset speed 1
Ground for reference and controls
Programmable
Range 0—20 mA/R
Differential receiver/transmitter
Differential receiver/transmitter
Control power supply backup
Relay output 1
Programmable
FAULT
Signal
Control voltage output; voltage for
switches etc.
Ground for reference and controls
Contact closed = Preset speed 2
Contact closed = Fault reset
Contact closed = Disable PID
Programmable
Active = Fault, stop according to defined
method
Signal
Voltage for potentiometer, etc.
Voltage input frequency reference (MF2-3)
Voltage/current input frequency reference
(MF4-MF6)
Can be programmed as DIN4
Ground for reference and controls
Voltage
reference
Ground for reference and controls
45(96)
Description
, max. 500 Ω
L
Description
Description
or
current
input
frequency
6