Fieldbus Parameters - Honeywell NXL User Manual

Honeywell welding system user manual
Hide thumbs Also See for NXL:
Table of Contents

Advertisement

7
80(96)
7.4.8.5

Fieldbus parameters

RS-485 communication status (I6.10.1)
With this function you can check the status of the RS 485 bus. If the bus is not in use, this value is 0.
xx = 0 – 64 (Number of messages containing errors)
yyy = 0 – 999 (Number of messages received correctly)
Fieldbus protocol (P6.10.2)
With this function you can select the fieldbus communications protocol.
Slave address (P6.10.3)
Set here the slave address for the Modbus protocol. You can set any address between 1 and 255.
Baud rate (P6.10.4)
Selects the baud rate used with the Modbus communication.
Stop bits (P6.10.5)
Set the number of stop bits used in Modbus communication
Parity type (P6.10.6)
Here you can select the type of parity checking used with the Modbus communication.
xx.yyy
0 = Not used
1 = Modbus protocol
0 = 300 baud
1 = 600 baud
2 = 1200 baud
3 = 2400 baud
4 = 4800 baud
5 = 9600 baud
6 = 19200 baud
7 = 38400 baud
8 = 57600 baud
0 = 1 stop bit
1 = 2 stop bits
0 = None
1 = Odd
2 = Even
Control Keypad
Honeywell
Honeywell
Honeywell
Honeywell

Hide quick links:

Advertisement

Table of Contents
loading