5.2

Cooling

Forced air flow cooling is used for NXL HVAC and NXL Compact size MF3.
Enough free space shall be left above and below the frequency converter to ensure sufficient air
circulation and cooling. You will find the required dimensions for free space in the table below.
Type
NXL 0002-0006 2
NXL 0001-0005 5
HVAC 03-12
HVAC 16-31
HVAC 38-61
Table 5-4. Mounting space dimensions
= clearance around the freq. converter (see also B)
A
= distance from one frequency converter to another or
B
distance to cabinet wall
= free space above the frequency converter
C
= free space underneath the frequency converter
D
Table 5-5. Required cooling air
Installation
Dimensions [mm]
A
B
C
10
10
100
10
10
100
20
20
100
20
20
120
30
20
160
Type
HVAC 03—12
HVAC 16—31
HVAC 38—61
D
C
50
50
50
60
80
A
D
Figure 5-6. Installation space
Cooling air required [m
70
190
425
Honeywell
Honeywell
Honeywell
Honeywell
B
B
A
NK5_2
3
/h)