NXS VARIABLE FREQUENCY DRIVES

Control Characteristics

Control Method
Switching Frequency:
FR4 – FR6 (1.1-30kW)
NXS0003...- NXS0061...
FR7 – FR9 (37-160 kW)
NXS0072...- NXS0310...
Frequency reference:
Analogue input
Keypad reference
Field Weakening point
Acceleration time
Deceleration time
Braking torque

Ambient Conditions

Ambient operating Temperature:
Low overload
(for Fan/Pump)
Storage temperature
Relative humidity
Air quality:
Chemical vapors
Mechanical particles
Altitude
Relative humidity
Vibration:
EN50178/EN60068-2-6
Shock:
EN50178, IEC 68-2-27
EN0B-0620GE51 R1107
Frequency Control U/f, Open-
Loop Sensorless Vector
Control
1...16 kHz;
Default: 10 kHz (no derating)
1...10 kHz
Default: 3.6 kHz
Resolution 0.1% (10 bit),
accuracy ±1%
Resolution 0.01 Hz
8...320 Hz
0...3000 sec
0...3000 sec
DC-brake: 30%*TN (without
brake option)
-10°C (no frost)...+45°C
(with 24 h average +40°C)
-40...+70°C
0...95% RH, non-condensing,
non-corrosive, no dripping
water
IEC 721-3-3, unit in operation,
class 3C2
IEC 721-3-3, unit in operation,
class 3S2
100% load capacity (no
derating) up to 1000 m
-1% derating for each 100 m
above 1000 m; max. 3000 m
0...95% RH, non-condensing,
non-corrosive, no dripping
water
5...150 Hz
Displacement amplitude 1 mm
(peak) at 5...15.8 Hz
Max acceleration amplitude
1 G at 15.8...150 Hz
UPS Drop Test (for applicable
UPS weights)
Storage and shipping: max
15 G, 11 ms (in package)
Enclosure class
Electro Magnetic Compatibility (EMC)
Immunity
Emissions:
Standard in all
Integrated option in:
FR4 – FR6 (1.1-30kW)
NXS0003...- NXS0061...
Safety
EN50178, EN60204-1, CE, GOST R, IEC 61800-5 (see unit
nameplate for more detailed approvals)

Control Connections

Analogue input voltage
Analogue input current
Digital inputs
Auxiliary voltage
Output reference voltage +10 V, +3%, max. load 10 mA
Analogue output
Relay outputs
Digital output
Motor thermistor Input
2
IP21 : NXS___ V35A2...
IP54 : NXS___ V35A5...
Complies with EN50082-1, -2,
EN61800-3
EMC-level H: EN 61800-3
(2004) Cat C2, EN 55011
Class A
EMC level C: EN 61800-3
(2004) Cat C1, EN 55011
Class B
0...+10 V, Ri = 200 kΩ,
resolution 10 bit, accuracy ±1%
0(4)...20 mA, Ri = 250 Ω
differential resolution 0.1%,
accuracy ±1%
6 positive logic; 18...24 Vdc
+24 V, ±15%, max. 100 mA
0(4)...20 mA; RL max. 500Ω;
resolution 16 bit; accuracy ±1%
2 programmable change-over
relay output (1 NO/NC and 1
NO). Switching capacity:
24 Vdc / 8 A, 250 Vac / 8 A,
125 Vdc / 0.4 A. Min. switching
load: 5 V / 10 mA
Open collector output, 50 mA /
48 V
R
= 4.7 kΩ (PTC),
TRIP
electrically isolated