Start-up wizard

NXL has a built-in start-up wizard, which speeds up the programming of the drive. The wizard helps
you choose between four different operating modes, Standard, Fan, Pump and High Performance.
Each mode has automatic parameter settings optimised for the mode in question. The programming
wizard is started by pressing the Stop button for 5 seconds, when the drive is in stop mode. See the
figure below for the procedure:
START-UP WIZARD
START
Honeywell
+
-
ENTER
reset
Push 5 seconds
1
to activate (in
stop mode)
0
50
3
3
I *1,5
400
H
Hz
Hz
s
s
Standard
20
50
20
20
I *1,1
400
L
Hz
Hz
s
s
Fan
20
50
5
5
I *1,1
400
L
Hz
Hz
s
s
Pump
0
50
1
1
I *1,8
400
H
Hz
Hz
s
s
High
performance
Figure 7-3. NXL Start-up wizard
Note! See the Application manuals for detailed parameter descriptions.
=
Start button.
Pressing this button starts the motor if the keypad is the active control
place. See Chapter 7.4.3.1.
=
Stop button.
Pressing this button stops the motor (unless disabled by parameter P3.4).
Stop button serves also for activating the Start-up Wizard (see below)
=Push the button
MODE
Honeywell
+
+
-
-
ENTER
reset
Accept
Select the
3
2
mode. See
table below!
50
0=
0=
0=
0=
*
Hz
Ramp
Coasting
Not
Ai1
V
used
0-10V
used
50
0=
0=
0=
0=
*
Hz
Ramp
Coasting
Not
Ai1
V
used
0-10V
used
**
50
0=
1=
0=
0=
*
Hz
Ramp
Ramp
Not
Ai1
V
**
used
0-10V
used
50
0=
0=
1=
0=
*
automatic
V
Hz
Ramp
Coasting
Ai1
torque
0-10V
used
boost
Control Keypad
rpm
n
Honeywell
rpm
+
-
ENTER
reset
Tune
Accept
5
4
n(rpm)
0=
I/O
Not
0=
I/O
Not
0=
I/O
Not
0=
I/O
Not
*In drives of 208V...230V
this value is 230V
I
(A)
n
Honeywell
A
+
-
ENTER
reset
Accept
Tune
6
7
I(A)
M
NOTE! Startup Wizard resets all
other parameters to factory
defaults!
** In NXL HVAC the default start function for Fan or Pump
mode is 2 = Conditional Flying Start which is
recommended start function with Trip Free Output
Switching function enabled as standard.