On every Battery, Power or Control Module are two LEDs to help inform the user of the module status.
Refer to the chart below:
Status LED
Fault LED
(Green)
( Amber)
OFF
OFF
OFF
ON
FLASHING
OFF
FLASHING
FLASHING
FLASHING
ON
OFF
FLASHING
ON
OFF
ON
ON
ON
FLASHING
* If this persists for more than 10 seconds, check to verify the lever is in the down position, otherwise the module is
faulty.
** If both Green and Amber LEDs are flashing for more than 30 seconds, then re-insert module.
Module LED Indication
Module Status
Module not inserted into frame.
System is OFF.
Module is initializing (max 30 seconds*).
Normal Operation
Module is in start-up qualification mode, or module warning. **
Module failed, is off-line and module control is functioning.
Abnormal operation, re-insert module. If this persists, contact qualified
assistance.