Simpleset Tm Field Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26 - ICM Controls SC 5011 Installation, Operation & Application Manual

Programmable electronic thermostat
Table of Contents

Advertisement

This feature is used for transferring configuration and program schedule from the master to the target
thermostat . All thermostats for a job can be mounted and powered up . Configure and program one
thermostat . This will be the master . The master will be used to copy the program to the rest of the
thermostats .
Preparing the master to Send:
1 . The master must be powered with 24 VAC .
2 . Verify the master thermostat is in OFF mode .
3 . Press SYS (left) button until OFF mode displays .
4 . Remove cover of the master thermostat by gently pulling near one of the corners
at the top of the thermostat .
5 . Press the up and down buttons and CONFIG switch simultaneously for 5 seconds .
6 . The OUT screen displays indicating the master thermostat is ready to transfer data .
Note: Press the up and down buttons and CONFIG switch simultaneously for 5
seconds to exit from data transfer mode and to return the master to the
OFF mode .
7 . Turn off power to the master and remove it from the wall .
8 . Connect the master to the target using the 3 wire connector . Attach one end to
the Master's FP pins and the other end to the Target's FP pins .
Note: Target thermostat must be powered with 24 VAC for field
programming to occur
When the connection has been made correctly, the master thermostat will power up and the target will
count from 5 down to 1 . It will then display the LOCK confirming the data has been saved in memory .
When all target thermostats have been completed, reinstall the master thermostat .
Press the up and down buttons and the CONFIG switch simultaneously for 5 seconds to exit from the
data transfer mode and to return the master thermostat to the OFF mode .

SimpleSet
Requires SimpleSet
Field Programming
TM
Transfer Cable (ACC-WIH21)
TM
OFF
FP pins
S1 S2 Y
W