Remote Or Outdoor Sensor Installation (Optional) - ICM Controls SC 5011 Installation, Operation & Application Manual

Programmable electronic thermostat
Table of Contents

Advertisement

Remote or Outdoor Sensor Installation (Optional)

1 . Remove cover from remote sensor housing .
2 . Select an appropriate location for mounting the remote sensor .
3 . Mount remote sensor unit using hardware provided .
4 . Install two strand shielded wire between remote sensor and thermostat . Shielded wire must be used . Do not
run remote sensor wire in conduit with other wires .
• Wire 1 should run between the S1 terminal on the thermostat and the S1 terminal on the remote sensor
• Wire 2 should run between the S2 terminal on the thermostat and the S2 terminal on the remote sensor
• Connect the shielding of the wire to the S2 terminal on the thermostat
5 . Configure the thermostat to operate with the remote sensor (see Configuration Mode setting 10, Page 14) .
Remote Sensor: (Shown: Optional ICM ACC-RT103 Remote Indoor Sensor;
for outdoor sensor, order ACC-OD103.)
Note: Remote or outdoor sensor reading can be displayed by
simultaneously pressing the Down and SYS buttons .


Hide quick links: