Vi. Water Piping and Trim (continued)
Table 13: Fitting and Valve Equivalent Length
Copper Fitting and Sweat Valve
Equivalent Length (Ft)
Fitting or Valve
Description
90° Elbow
45° Elbow
Tee (thru flow)
Tee (Branch flow)
Diverter Tee (typical)
Gate Valve
Globe Valve
Angle Valve
Ball Valve (standard port)
Ball Valve (full port)
Swing Check Valve
Flow-Check Valve (typical)
Butterfly Valve
NOTE: Table 13 is provided as reference to assist in piping design and specifies equivalent length of typical piping fittings and
valves.
The alpine (aLP) boiler heat exchanger is made from stainless steel tubular coil having relatively narrow
waterways. Once filled with water, it will be subject to the effects of corrosion. Failure to take the following
precautions to minimize corrosion and heat exchanger waterways overheating could result in severe boiler
damage.
Before connecting the boiler, insure the system is free of impurities, grease, sediment, construction
dust, sand, copper dust, flux and any residual boiler water additives. Flush the system thoroughly and
repeatedly, if needed, with clear water mixed with concentrated rinse agent to remove these contaminants
completely.
iron oxide (red oxide sludge Fe
in the system, the system must be air free and leak tight. Do not connect the boiler to radiant tubing
without an oxygen barrier. Using automatic water refill is not recommended, however, if such refill is
employed, a water meter must be added to evaluate the makeup water volume taken after initial fill and
eliminate any water leakage as early as possible.
Maintain the water pressure in the boiler at a minimum of 12 PSi.
The boiler water pH must be within 8.2 < pH < 9.5. if the system contains any aluminum components,
pH must be less than 8.5.
Black oxide sludge (magnetite Fe
system not protected by an inhibitor.
Scale deposit is made up of lime scale contained in most distributed water and settles over the warmest
surfaces of boiler heat exchanger causing subsequent overheating and eventual failure. Water hardness
must be maintained within  to 9 grain/gal range.
Refer to Section Xiii "Service and Maintenance" for recommended heating system water treatment
products (corrosion/scale inhibitors, cleaners etc) and their suppliers.
Copper Pipe or Valve Size
1
2.5
3.0
4.0
5.5
1.0
1.2
1.5
2.0
0.5
0.6
0.8
1.0
4.5
5.5
7.0
9.0
23.5
25.0
23.0
23.0
0.3
0.4
0.5
0.7
25.0
36.0
46.0
56.0
5.3
7.8
9.4
12.5
4.3
7.0
6.6
14.0
1.9
1.4
2.2
1.3
4.5
5.5
6.5
9.0
54.0
74.0
57.0
177.0
2.7
2.0
2.7
4.5
O
) is produced during oxygenation. To minimize any oxygen presence
2

O
) forms as the result of continuous electrolytic corrosion in any


Table 13: Fitting and Valve Equivalent Length
(cont'd)
Threaded Fitting and Valve Equivalent Length (Ft)
Fitting or Valve
2
Description
90° Elbow
Long Radius
Elbow (45° or 90°)
Tee (thru flow)
Tee (Branch flow)
Close Return Bend
Gate Valve (full open)
Globe Valve (full open)
Angle Valve (full open)
Swing Check Valve
(full open)
Flow-Check Valve (typical)
nOTiCE
Black Threaded Pipe or
Valve Size
1
2.6
3.5
4.0
1.4
1.8
2.2
1.8
2.3
2.7
5.3
6.9
8.1
10.0
4.4
5.8
6.7
0.7
0.9
1.1
30.0
39.0
46.0
59.0
13.0
17.0
20.0
26.0
8.7
12.0
13.0
17.0
42.0
60.0
63.0
83.0
2
5.2
2.8
3.5
8.6
1.4
5