Burnham ALPINE Installation, Operation And Service Instructions page 43

Alpine series condensing high efficiency direct vent gas - fired hot water boiler
Hide thumbs Also See for ALPINE:
Table of Contents

Advertisement

Vi. Water Piping and Trim (continued)
Table 11: Flow Range Requirement Through Boiler
Boiler
Boiler
Boiler
Supply
Return
Connection,
Connection,
Model
Inch, FPT
Inch, FPT
ALP080
1
ALP105
1
ALP150
1
ALP210
1
ALP285
ALP399
ALP500
Notes: Required Flow (GPM) = ** Output (MBH) x 1000/500 x DT
** Output (MBH) - Select Value for specific Boiler Model from Tables 2A or 2B
Using boiler antifreeze will result in higher fluid density and may require larger circulators.
Minimum
Boiler
Required Flow
Head Loss,
(GPM)
@ 35°F DT
@ 35°F DT
1
4.2
1
5.5
1
7.9
1
11.1
15.1
21.5
27.0
Alpine Boiler Head Loss vs. Flow
25
20
105
15
10
150
5
80
0
0
5
10
15
Required
Boiler Head
Flow,
Loss,
(GPM)
Ft.
Ft.
@ 30°F DT
@ 30°F DT
4.8
4.9
6.4
7.0
6.4
9.3
5.2
9.2
6.6
5.4
12.9
7.1
5.9
17.7
7.8
6.1
25.1
7.9
6.8
31.5
8.8
285
399
210
20
25
30
Flow Rate (GPM)
Required
Maximum
Flow,
Boiler Head
Required
(GPM)
Loss, Ft. @
Flow (GPM)
@ 25°F
25°F DT
@ 20°F DT
DT
5.8
8.9
7.7
12.8
11.0
8.9
15.5
9.8
21.2
10.7
30.2
10.8
37.8
12.0
500
35
40
45
50
Boiler
Head Loss,
Ft.
@ 20°F DT
7.3
13.4
9.6
19.1
13.8
12.7
19.4
14.4
26.5
16.0
37.7
15.9
47.2
17.4