Xii. Operation (continued)
E.

Adjusting Parameters

From the "Home" screen select the Adjust button to access the adjustment mode screens show below (if required, refer to the
previous page to review how to enter Adjustment mode):
The following pages describe
Sage2.1's adjustable parameters.
Parameters are presented in the order
they appear on the Sage2.1 Display,
from top to bottom and, left to right
System
Setup
"Press"
button to access the following parameters:
Factory
Range /
Setting
Choices
Fahrenheit,
Fahrenheit
Celsius
30%
0-100%
30%
0-100%
Not Installed,
Installed
Installed
Disabled
Enable/Disable
Disabled
Enable/Disable
70°F
0-100°F
102
Temperature Units
The Temperature Units parameter determines whether temperature is represented in units of Fahrenheit or
Celsius degrees.
Display Brightness
Display brightness is adjustable from 0 to 100%.
Display Contrast
Display contrast is adjustable from 0 to 100%.
Outdoor Sensor Source
Not Installed
Outdoor Sensor is not connected to the boiler, the sensor is not monitored for faults.
Installed
Outdoor Sensor is installed and monitored for faults.
note: Enabling Frost Protection, Warm weather shutdown or Outdoor Air Reset functions will automatically
install the outdoor sensor. If you choose to disable these features and not use the outdoor sensor, press the "Not
Installed" selection to remove the outdoor sensor from fault monitoring screens.
Frost Protection
Disable
Frost Protection is not used.
Enable
Boiler and system circulators start and boiler fires when low outside air, supply and return
temperatures are sensed as follows:
Device
Boiler & System
Pump
Boiler
Warm weather shutdown enable
Disable
Warm Weather Shutdown (WWSD) is not used.
Enable
The boiler will not be allowed to start in response to a central heat call for heat if the outside
temperature is greater than the WWSD setpoint. The boiler will still start in response to a
Domestic Hot Water call for heat.
Warm weather shutdown setpoint
The Warm Weather Shutdown (WWSD) Setpoint used to shutdown the boiler when enabled by the "WWSD En-
able" parameter.
System
Setup
Pump
Setup
Manual
Control
Central
Heat
Outdoor
Reset
Sequencer
Master
Parameter and Description
Start
Temperatures
Temperatures
Outside Air < 0°F
Outside Air > 4°F
Supply Water < 45°F
Supply Water > 50°F
Supply Water < 38°F
Supply Water > 50°F
Modulation
Setup
Contractor
Setup
- More -
DHW
Remote
4-20mA
Sequencer
Slave
Stop