Hard Lockout Codes - Burnham ALPINE Installation, Operation And Service Instructions

Alpine series condensing high efficiency direct vent gas - fired hot water boiler
Hide thumbs Also See for ALPINE:
Table of Contents

Advertisement

XiV. Troubleshooting (continued)
C.
Troubleshooting problems where a Hard Lockout
Code is displayed. When a hard lockout occurs, the
boiler will shut down, the display will turn red and
the "Help" button will "blink". Select the "blinking"
Hard Lockout Codes Displayed
Lockout number
4
Supply high limit
5
DHW high limit
6
Stack High limit
12
Flame detected out of sequence
18
Light off rate proving failed
19
Purge rate proving failed
20
Invalid Safety Parameters
21
Invalid Modulation Parameter
22
Safety data verification needed
23
24VAC voltage low/high
24
Fuel Valve Error
25
Hardware Fault
26
Internal Fault
27
Unknown Fault
116
Condition
Sage2.1 supply sensor detected
temperatures in excess of 210°F.
Sage2.1 DHW sensor detected
temperatures in excess of Setpoint.
Sage2.1 Flue gas (Stack) sensor
detected temperatures in excess of
204°F.
A flame signal was present when there
should be no flame.
Blower is not running at Light-off rate
when it should or fan speed signal not
being detected by Sage2.1.
Blower is not running at Purge rate
when it should or fan speed signal not
being detected by Sage2.1.
Unacceptable Sage2.1 control Safety
related parameter detected.
Unacceptable Sage2.1 control
Modulation related parameter detected.
Safety related parameter change has
been detected and a verification has
not been completed.
Sage2.1 control 24Vac control power is
high or low.
Power detected at fuel valve output
when fuel valve should be off.
Internal control failure.
Internal control failure.
Unknown Fault
"Help" button to determine the cause of the Hard
Lockout. Once the condition that caused the lockout
is corrected, the boiler will need to be manually reset
using the Reset button on the "Active Fault" display or
located on the Sage2.1 Control.
Possible Cause
Heating load at time of error was far below the minimum firing
rate of the boiler.
Defective system pump or no flow in primary loop.
Defective boiler pump or no flow in boiler loop.
Control system miswired so that the boiler operation is
permitted when no zones are calling.
DHW load at time of error was far below the minimum firing
rate of the boiler.
Control system miswired so that boiler operation is permitted
when no DHW are calling.
Heat exchanger needs to be cleaned.
Boiler over-fired.
Air-fuel mixture out of adjustment - consult factory.
Defective gas valve - make sure inlet pressure is below
maximum on rating plate before replacing valve.
Loose connection in 120 VAC fan wiring.
Loose or miswired fan speed harness.
Defective fan
Loose connection in 120 VAC fan wiring.
Loose or miswired fan speed harness.
Defective fan
Safety Parameter verification required. Contact factory.
Reset the control.
Safety related Sage2.1 control parameter has been changed and
verification has not been performed.
Loose connection in 24Vac VAC power wiring.
Loose or miswired 24Vac harness.
Miswired wiring harness causing power supply short to
ground.
Defective transformer.
Transformer frequency, voltage and VA do not meet
specifications.
Loose or defective gas valve harness. Check electrical
connections.
Defective gas valve (check for 24 Vac at harness during trial
for ignition before replacing valve).
Reset the control. If problem reoccurs, replace the Sage.
Reset the control. If problem reoccurs, replace the Sage.
Reset the control. If problem reoccurs, replace the Sage.