Burnham ALPINE Installation, Operation And Service Instructions page 12

Alpine series condensing high efficiency direct vent gas - fired hot water boiler
Hide thumbs Also See for ALPINE:
Table of Contents

Advertisement

I. Product Description, Specifications and Dimensional Data (continued)
Table 2C: Rating Data - Models aLP150 thru aLP285 (001 to 10,000 Feet Elevation above Sea Level)
alpine Series gas-Fired Boilers
Input
(MBH)
Model
Number *
Min. Max.
ALP150
38
113
ALP210
53
158
ALP285
68
204
* Add Suffix "F" for Floor mounted Models or Suffix "W" for Wall mounted Models.
notes: ** DOE Heating Capacity (ALP150 thru ALP285)
Maximum Working Pressure, Water - 30 PSI Shipped from Factory (std.); 50 PSI - Optional
Maximum Allowable Temperature, Water - 210°F
Boilers are factory shipped as Natural Gas builds only.
Input has been de rated for noted elevation above sea level.
12
Net I=B=R
** Output
Ratings
(MBH)
Water (MBH)
104
90
145
126
188
163
Thermal
AFUE
Combustion
Efficiency
Efficiency (%)
%
(%)
95
95
95
Boiler Water
Heat Transfer
Volume
Area (Sq. Ft.)
(Gal.)
1.3
16.4
1.7
21.8
2.4
29.1

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Alp080Alp105Alp150Alp210Alp285Alp399 ... Show all

Table of Contents