Xii. Operation (continued)
E.
Adjusting Parameters (continued)
Remote
"Press"
button to access the following parameters:
4-20mA
Factory
Range /
Setting
Choices
Local,
Local
4-20mA
Local,
Local
4-20mA
80°F -
130°F
Central Heat
Setpoint
80°F -
130°F
Central Heat
Setpoint
* Only visible when Central Heat Setpoint Source is set to 4-20mA.
For Sequence Master and Sequence Slave menu explanation refer to Section XII "Modular Installation", Paragraph G, 4.
Central Heat Modulation Source
This parameter enables the 4-20mA input to control firing rate and the thermostat input to control
boiler on/off demand directly without using internal setpoint. The 4-20mA selection is used to enable a
remote multiple boiler controller to control the Sage2.1 Control:
Local:
4-20mA Input on Terminal 9 & 10 is ignored.
4-20mA
4-20mA Input on Terminal 9 & 10 is used to control firing Rate % directly.
Central Heat Setpoint Source
Sets the remote (Energy Management System) control mode as follows:
Local:
Local setpoint and modulation rate is used. 4-20mA input on Terminal 9 & 10 is ignored.
4-20mA
4-20mA Input on Terminal 9 & 10 is used as the temperature setpoint. The following two
parameters may be used to adjust the signal range.
Central Heat -20madc Setup,  ma Water Temperature*
Sets the Central Heat Temperature Setpoint corresponding to 4mA for signal input on terminal 9 & 10.
Voltage below 4mA is considered invalid, (failed or incorrect wired input).
Central Heat -20madc Setup, 20 ma Water Temperature*
Sets the Central Heat Temperature Setpoint corresponding to 20mA for signal input on terminal 9 &
10. Voltage above 20mA is considered invalid, (failed or incorrect wired input).