Adjustment Channels
Channel
Description
Arr
x
System
DT O
x
Switch-on temperature difference
DT F
x
Switch-off temperature difference
DT S
x
Nominal temperature difference
RIS
x
Rise control R1
nMN
x
Minimum pump speed
S MX
x
Maximum tank temperature
EM
x
Emergency temperature collector
CMX
s
Maximum collector temperature
OCN
x
Option minimum limitation
CMN
x*
Minimum collector temperature
OCF
x
Option antifreeze
CFR
x*
Antifreeze temperature
O TC
x
Option tube collector
TCST
x*
OTC starting time
TCEN
x*
OTC ending time
TCRU
x*
OTC runtime
TCIN
x*
OTC standstill interval
OHQM
x
Option energy metering
FMAX
x*
Maximum flow
MEDT
x*
Antifreeze type
MED%
x*
Antifreeze concentration (only if MEDT = propylene or ethylene)
MAN1
x
Manual operation R1
MAN2
x
Manual operation R2
LANG
x
Language
UNIT
x
Temperature unit
RESE
x
Reset - back to factory defaults
W0050100
Version number
Legend:
Symbol
x
Channel is available
x*
Channel is available if the corresponding option is activated.
s
Channel is specifically available in this system layout
Specification
Factory setting
Page
10
39
12.0 °Ra [6.0 K]
39
8.0 °Ra [4.0 K]
39
20.0 °Ra [10.0 K]
39
4 °Ra [2 K]
39
30 %
39
140 °F [60 °C]
40
270 °F [130 °C]
40
230 °F [110 °C]
41
OFF
42
50 °F [10 °C]
42
OFF
42
40.0 °F [4.0 °C]
42
OFF
44
07:00
44
19:00
44
30 s
44
30 min
44
OFF
44
6.0 l
44
1
44
45 %
44
Auto
46
Auto
46
En
46
°C
46
46