The controller calculates the temperature differences
between collector sensor S1 and tank sensors S2 and S3. If
the differences are larger than or identical to the adjusted
switch-on temperature differences (DT1O / DT2O), the
solar pump will be operated by relay 1, and the respective
tank zone will be loaded until the switch-off temperature
differences (DT1F / DT2F) or the maximum tank tempera-
Arr 4
S1
R1
R2
S4 / TR
Display Channels
Channel
Description
COL
x
Temperature collector
TSTB
x
Temperature tank 1 bottom
TSTT
x
Temperature tank 1 at the top
S4
x
Temperature sensor 4
TR
x*
Temperature return sensor
n %
x
Pump speed relay
hP1
x
Operating hours R1
hP2
x
Operating hours R2
x*
kWh
Heat quantity kWh
MWh
x*
Heat quantity MWh
TIME
x
Time
16
|
tures (S1MX / S2MX) are reached. The priority logic causes
priority loading of the upper zone of the tank, if possible.
The 3-way-valve will be operated by relay 2 then.
Sensor S4 can optionally be connected for measurement
purposes.
If energy metering (OHQM) is activated, sensor S4 has to
be connected as return sensor.