System Layout 9 - Viessmann SCU224 User Manual

Temperature controller
Table of Contents

Advertisement

SCU224

System layout 9

The controller calculates the temperature difference bet-
ween collector sensor S1 and tank sensor S2. If the diffe-
rence is larger than or identical to the adjusted switch-on
temperature difference (DT O), the solar pump will be
operated by relay 1, and the tank will be loaded until the
switch-off temperature difference (DT F) or the maximum
tank temperature (S MX) is reached.
Arr 9
S1
R1
Display Channels
Channel
Description
INIT
x*
ODB initialization active
x*
FLL
ODB filling time active
STAB
x*
ODB stabilization in progress
COL
x
Temperature collector
TSTB
x
Temperature tank 1 bottom
TSTT
x
Temperature tank 1 at the top
TRET
x
Temperature heating circuit
n %
x
Pump speed relay
hP1
x
Operating hours R1
hP2
x
Operating hours R2
TIME
x
Time
28
|
A heating circuit return preheating will be operated by
relay 2, if the temperature difference between sensors S3
and S4 is larger than or identical to the adjusted switch-on
temperature difference (DT3O). For this purpose, relay 2
will operate the 3-way-valve.
S3
S2
S4
R2