System Layout 3 - Viessmann SCU224 User Manual

Temperature controller
Table of Contents

Advertisement

SCU224

System layout 3

The controller calculates the temperature difference bet-
ween collector sensor S1 and tank sensor S2. If the diffe-
rence is larger than or identical to the adjusted switch-on
temperature difference (DT O), the solar pump will be
operated by relay 1, and the tank will be loaded until the
switch-off temperature difference (DT F) or the maximum
tank temperature (S MX) is reached.
Sensor S3 is used for a thermostatic function, which ope-
Arr 3
S1
R1
S4 / TR
Display Channels
Channel
Description
INIT
x*
ODB initialization active
x*
FLL
ODB filling time active
STAB
x*
ODB stabilization in progress
COL
x
Temperature collector
TSTB
x
Temperature tank 1 bottom
TSTT
x
Temperature tank 1 at the top
TDIS
s*
Thermal disinfection temperature
S4
x
Temperature sensor 4
TR
x*
Temperature return sensor
n1 %
x
Pump speed R1
h P1
x
Operating hours R1
h P2
x
Operating hours R2
kWh
x*
Heat quantity kWh
MWh
x*
Heat quantity MWh
s*
CDIS
Countdown of monitoring period
SDIS
s*
Starting time display
s*
DDIS
Heating period display
TIME
x
Time
12
|
rates relay 2 for backup heating or heat dump purposes,
when the adjusted thermostat switch-on temperature
(AH O) is reached. This function can optionally be com-
bined with up to three adjustable time frames.
Sensor S3 can also be optionally used as a reference sensor
for the thermal disinfection function OTD.
Sensor S4 can optionally be connected for measurement
purposes. If energy metering (OHQM) is activated, sensor
S4 has to be connected as return sensor.
S3
R2
S2
Terminal
Page
-
37
-
37
-
37
S1
37
S2
37
S3
37
S3
37
S4
37
S4
37
R1
38
R1
38
R2
38
-
38
-
38
-
38
-
38
-
38
-
34

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents