CAUTION
Failure of the solenoid plunger to bottom in the solenoid will result in a failed solenoid.
To avoid failure ofthe solenoid, make sure the solenoid plunger bottoms in the solenoid. Check
the solenoid's operation at the initial start-up. Periodically lubricated linkage joints between
the solenoid plunger and the throttle arm will eliminate binding.
NOTE: The solenoid plunger
must
move smoothly and rapidly into the solenoid when the
solenoid is electrically energized, drawing the engine's throttle arm into the Set Speed/Run
position.
To arrive at the appropriate frequency, either monitor the speed of the engine/generator with a tachometer,
or monitor the frequency with a frequency meter, the latter method being the more precise of the two.
Make sure 10 - 12 volts DC is present at the solenoid's positive
(+)
harness connection during PREHEAT
and START. Loss of voltage will affect the solenoid's operation and cause a solenoid failure.