Westerbeke BCD 4.4KW Operator's Manual page 44

Marine diesel generator sets
Hide thumbs Also See for BCD 4.4KW:
Table of Contents

Advertisement

E. Place the positive (
+)
lead on point #1 and the negative (-) lead on point #3. The Ohmmeter again
should not register any deflection (no deflection indicated infinite resistance). Reverse these connec-
tions and the Ohmmeter should again register no deflection. IF THE RECTIFIER FAILS ANY OF THE
PREVIOUS TESTS (A - E), REPLACE THE RECTIFIER BECAUSE IT IS DEFECTIVE.
4. Integral Control/er (I.C.)
The integral controller (I.C.) is an encapsulated, solid-state unit that supplies a DC charging voltage to the
generator's starting battery while the generator is operating.
Charging Voltage:
13.0 -14.0 Volts DC
Charging Amperage:
0 - 10 Amps DC
A separate group of stator windings supplies AC voltage to a bridge rectifier which converts the AC current
into DC current to supply the I.C. unit. The I.C. unit senses the needs of the starting battery and supplies a
DC charge when one is needed. If you suspect that the I.C. unit is faulty (that is, if the battery's charge is
low), check the charging circuit's operating and components as described in steps 1-4. Check all connec-
tions for cleanliness and tightness including the ground before replacing the I.C. unit.
NOTE: When the generator is first started, the I.C. unit will produce a low charging rate. This charging
rate will rise as the generator is operated for awhile.
41
Westerbeke Generator