4-Pole
Generator
Voltage
Load
Speed
Frequency
120V (110)
240V (220)
Applied
(rpm)
(Hertz)
Plants
Plants
None
1830
62
122
240
(1530)
(52)
(112)
(224)
Half
1800
60
120
240
(1500)
(SO)
(110)
(220)
Full
1755
59
110
220
(1455)
(49)
(100)
(200)
The output voltage should
be
checked periodically to ensure proper operation of the generating plant and
the appliances it supplies.
If an AC vottmeter or ampmeter is not installed to monitor voltage and load
I
check it with a portable meter
and amp-probe.
Preventive Maintenance (Generator)
Maintenance on the generator is minimal.
1. Keep the generator clean, dry and well-ventilated.
2. Make sure all connections are clean and tight and that cables carrying AC voltage are properiy supported
and protected against chafing.
3. The rear armature bearing is lubricated and sealed; therefore, no maintenance is required. If the bearing
becomes rough or noisy, replace it.
Generator Troubleshooting
A complete and illustrated text on troubleshooting the BC series of generators is furnished in booklet form
and incorporated in the Technical Manual which is available through your local dealer.