REMOTE PANEL INSTALLATION
INSTALLER'S/OWNER'S RESPONSIBILITY
1.
Wiring between the generator set and either a remote start panel
or
remote
instrument
panel
must
comply
with
u.S.
Coast
Guard
Safety Regulations 33 CFR-183.
2.
The mimimum voltage required at the starter solenoid is 9 volts.
3.
Therefore, wire gauges from TBl-l to TB3-l and from TBl-2 to TB3-2
should be selected to give a maximum voltage drop of 1 volt or
less.
This will provide 9 volts at the starter solenoid when bat-
tery terminal voltage is down to 10 volts, indicative of a deeply
discharged battery.
Where #16 wire is shown in the table of Minimum Wire Gauges below,
we
recommend
using
#14
wire
for
greater
strength and/or
lower
voltage drops.
MINIMUM WIRE GAUGES (AWG)
Wire Length from Generator to Remote Panel
Terminals
0-16'
16-20'
20-25'
25-32'
32-40'
40-50'
50-65'
TB1-1 to TB3-1
#12
#10
#10
#8
#8
#6
#6
TB 1-2 to TB3-2
14
12
12
10
10
8
8
TB2-1 to TB4-1
14
14
12
10
10
8
8
TB2-2 to TB4-2
14
14
14
14
14
14
14
TB2-3 to SENDER
14
14
14
14
14
14
14
TB2-4 to SENDER
14
14
14
14
14
14
14
TB2-5 to TB4-3
14
14
14
14
14
14
14
88