Westerbeke 7.6 KW BTD 60Hz Operator's Manual page 62

Marine diesel generator set
Table of Contents

Advertisement

Load Applied
4-Pole Speed
Frequency
Generator
Voltage
(rpm)
(Hertz)
120V (110)
240V (220)
Plants
Plants
None
1830
62
122
240
(1530)
(52)
(ll2)
(224)
Half
1800
60
120
240
(1500)
(50)
(110)
(220)
Full
1755
59
110
220
(1455)
(49)
(100)
(200)
The output voltage should be checked periodically to ensure proper operation of the generating plant and
the appliances it supplies.
If an AC voltmeter or ampmeter is not installed to monitor voltage and load, check it with a portable
meter and amp-probe.
Preventive Maintenance (Generator)
Maintenance on the generator is minimal.
1. Keep the generator clean, dry and well-ventilated.
2. Ensure that all connections are clean and tight and that cables carrying AC voltage are properly
supported and protected against chafing.
3. The rear armature bearing is lubricated and sealed; therefore, no maintenance is required. If the
bearing becomes rough or noisy, replace it.
Generator Troubleshooting
A complete and illustrated test on troubleshooting the BID series of generators is furnished in the
Technical Manual which is available through your local dealer.
WESTERBEKE GENERATORS
58