sYstem test Fan: oPtIonal
If continuing from the previous section on this page, skip to Step 2 below. The following
instructions assume that the user enters the Service Menus from the home screen display;
it does not assume that the user has followed in sequence from the previous section.
1. On the thermostat, press the lower left and lower right keys simultaneously for about
fi ve seconds. Next,
Back, and
Go
2. Press
until Service Menu 620 appears in the display.
Next
( The default value for Service Menu appears below Service Menu.)
Figure 12.
Service Menu
620 allows
the user to
perform a
System Test
Fan.
3. In Service Menu 620, press ▲/ ▼to select option "01" to enable fan output
(see Fig. 13).
note: If 1 is selected, the thermostat will activate the associated output for 10 minutes.
The user should observe that the fan output will turn on.
Figure 13.
Press Done
to complete
testing and
exit Service
Menus,
or Next to
continue tests.
4. Press
to complete the system test. After verifying the system test, the outputs
Done
are disabled.
optional: the user may also perform system test main output (cool):see table 2,
service menu 600.

User oPeratIon

For detailed instructions on user operation of the T4000 Series, including how to operate
all key functions, please refer to the Performance PRO T4000 Series Operating Manual,
the companion to this installation guide.
© COPYRIGHT 2010 PECO, INC. ALL RIGHTS RESERVED.
appear (see Fig. 12).
Done
Service Menu
Default value
(appears
automatically)
Part X: set PIn access For servIce menUs (oPtIonal)
Creating a PIN access code allows the installer to restrict access to Service Menus. First,
PIN access must be enabled in Service Menu 341; second, a three-digit code must be
created in Service Menu 342. After these two Service Menus are properly confi gured, the
thermostat requires the user to enter a PIN access code to enter the Service Menus.
1. On the thermostat, press the lower left and lower right keys simultaneously for about
fi ve seconds. Next,
Back, and
Go
2. Press
until Service Menu 341 (Enable/Disable PIN Access) appears in the
Next
display. (Default value "00" appears below Service Menu.)
3. In Service Menu 341, press ▲/ ▼to change digit (fl ashing) value to "01" (see Fig. 14).
note: selecting 01 enables PIn access for the thermostat service menus, and
selecting it is necessary to show service menu 342.
4. Press Next.
5. In Service Menu 342, press ▲/ ▼adjust values and create a three-digit PIN access
code. The fl ashing three-digit code appears in the clock area (see Fig. 15).
note: write down the PIn access code, and keep it in a safe place.
6. Press
when fi nished.
Done
verIFY PIn access coDe
Enter the PIN access code upon entering the Service Menus. Note: Flashing digit is active;
it is changed using the ▲/ ▼keys. The active (editable) digit moves from right to left.
1. On the thermostat, press the lower left and lower right keys simultaneously for about
fi ve seconds. note Flashing three-digit code, Next, and
2. Press ▲/ ▼to change value of digit furthest to the right, then press Next.
3. Press ▲/ ▼to change value of digit in middle, then press Next.
4. Press ▲/ ▼to change value of digit furthest to left, then press Done.
note: After step 4 is complete, user is allowed access to Service Menus. Next,
and Service Menu 100 appear.
Go
Back,
Done,
Flashing
three-digit
code
5
appear (see Fig. 14).
Done
Service Menu
user to restrict
Service Menu
user to create
a PIN access
Flashing
three-digit
code
appear (see Fig. 16).
Done
code fl ashes
enters Service
Menus (after
enabling PIN
P/N 70476 3220-2265 REV 00
Figure 14.
341 allows
access to
Service
Menus.
Figure 15.
342 allows
code.
Figure 16.
PIN access
when user
access).