D. Chimney Termination Requirements
Follow manufacturers instructions for clearance, securing,
flashing and terminating the chimney.
•
Must have an approved and listed cap
•
Must not be located where it will become plugged by
snow or other material
•
Must terminate at least feet (91cm) above the roof
and at least 2 feet (61cm) above any portion of the
roof within 10 feet (05cm)
•
Must be located away from trees or other struc-
tures
E. 2-10-3 Rule
These are safety requirements and are not meant to assure proper flue draft.
ft. (91cm)
Minimum
Figure 19.1
Figure 19.2
September 1, 2008
2 ft. (61cm)
10 ft. (05cm) To Nearest Roofline
10 ft. (05cm) or more
Wall or Parapet
ft. (91cm) Minimum
NOTE:
•
Chimney performance may vary.
•
Trees, buildings, roof lines and wind conditions affect
performance.
•
Chimney height may need adjustment if smoking or
overdraft occurs.
Less than 10 ft. (05cm)
2 ft. (61cm)
Pitched Roof
ft. (91cm) Minimum
Flat Roof
7037-135E
4300 Wood Stove Series (ACC)
ft. (91cm)
Minimum
Less than 10 ft. (05cm)
2 ft. (61cm)Minimum