Chimney Termination Requirements; 2-10-0 Rule - Quadra-Fire 43M-ACC-MBK Owner's Manual

4300 wood stove series advanced combustion control (acc) installation and operation
Table of Contents

Advertisement

R
D. Chimney Termination Requirements
Follow manufacturers instructions for clearance, securing,
flashing and terminating the chimney.
Must have an approved and listed cap
Must not be located where it will become plugged by
snow or other material
Must terminate at least  feet (91cm) above the roof
and at least 2 feet (61cm) above any portion of the
roof within 10 feet (05cm)
Must be located away from trees or other struc-
tures
E. 2-10-3 Rule
These are safety requirements and are not meant to assure proper flue draft.
 ft. (91cm)
Minimum
Figure 19.1
Figure 19.2
September 1, 2008
2 ft. (61cm)
10 ft. (05cm) To Nearest Roofline
10 ft. (05cm) or more
Wall or Parapet
 ft. (91cm) Minimum
NOTE:
Chimney performance may vary.
Trees, buildings, roof lines and wind conditions affect
performance.
Chimney height may need adjustment if smoking or
overdraft occurs.
Less than 10 ft. (05cm)
2 ft. (61cm)
Pitched Roof
 ft. (91cm) Minimum
Flat Roof
7037-135E
4300 Wood Stove Series (ACC)
 ft. (91cm)
Minimum
Less than 10 ft. (05cm)
2 ft. (61cm)Minimum
Page 19