Download Print this page

HearthStone Champlain 8300 Owner's Manual And Installation Manual page 38

Gas-fired direct vent heater

Advertisement

HearthStone Quality Home Heating Products Inc
TROUBLESHOOTING
Symptom
Possible Cause
3. Pilot burning, no
A. Thermostat switch or
gas to main burner,
wires defective.
valve knob in the
"ON" position,
thermostat and/or
on/off/t'stat switch
in the "ON"
position.
B. Thermopile may not be
generating sufficient voltage. B. Check thermopile output, using a milli-volt
C. Plugged burner orifice.
A. Inconsistent, of
4. Pilot and burner
insufficient flame on
come on, but go
thermopile.
out after some
warm-up.
B. Insufficient gas pressure. B. Check line pressure to ensure that the
5. Frequent pilot
A. Pilot flame may be too
outrage problem.
low or blowing, (high),
causing the pilot safety to
drop out.
6. Glass fogs
A. A normal result of gas
combustion.
7. Blue Flames
A. A normal result during the
first 20 minutes.
CHAMPLAIN Gas-Fired Direct Vent
Corrective Action
A. Check thermostat/wiring for proper
connections. Place jumper wire across
terminals at thermostat. If burner comes on,
replace defective thermostat. If not OK, place
jumper across thermostat wires at gas valve.
If burner comes on, tighten connections, or
replace faulty wires.
meter. If the optional on/off kit has not been
installed, take the readings across generator
terminals of the gas valve. TPTH and TP).
With the on/off kit, take the readings across
TH and Terminal block (which corresponds to
#3 on the switch). Milli-volt reading should be
greater than 325 mV. If not, replace the pilot
assembly. If the meter reading is OK, but the
burner does not come on, replace the gas
valve.
C. Remove and check burner orifice, clean or
replace. Note: do not use any metal cleaning
device, as this may damage the orifice.
A. Adjust pilot flame size and assure that the
flame is aimed directly at the thermopile.
correct inlet pressure is present for the type
of gas being used. If propane pressure is
inconsistent, check for water condensation at
the regulator.
A. Clean and/or adjust the pilot flame for
maximum impingement on the thermopile
and thermocouple.
A. After the heater has warmed up, the glass
should clear.
A. Flames should begin to turn more
yellowish after 20 minutes of burning.
B. If the blue color stays; adjust the air
shutter for a proper burn.
38

Advertisement

loading

This manual is also suitable for:

Champlain