Hearth Requirements; Suitable Fireplace Dimensions; Safety Information - Osburn 2200 Owner's Manual

Us environmental protection agency phase ii certified wood insert
Hide thumbs Also See for 2200:
Table of Contents

Advertisement

2.1.1 Hearth Requirements

If the non-combustible hearth is flush with the floor, then the hearth must be 16"
(406mm) in front of the fan housing (see Figure 2.1.2). If the non-combustible hearth is a
minimum of 4" (102mm) above the floor, then the hearth can be 6" (152mm) out from
the fan housing with a 10" (254mm) floor protection (sparks) extended beyond the hearth
(see Figure 2.1.1). The non-combustible hearth must be a minimum of 8" (203mm) on
each side of the unit (Canada & US).

2.2 Suitable Fireplace Dimensions

2.3 Safety Information

NOTE:
This appliance is not recommended for use in a home if an occupant has any
respiratory or any other related problems.
1. It is important to follow the installation and operation instructions. An improperly installed or
operated insert could result in a safety hazard or fire, or damage to the unit, which would not be
covered by the warranty. Contact local building or fire officials about restrictions and installation
requirements in your area. You should be familiar with the installation and be sure that the work is
done in accordance with this manual.
WARNING: DO NOT INSTALL THIS INSERT IN A SLEEPING ROOM.
Figure 2.1.1
MEASUREMENT FOR
Opening Height (F)
Opening Width (G)
Opening Depth (H)
Table 2.2
Figure 2.1.2
MINIMUM
21.75" (553mm)
28"
(711mm)
17.8" (452mm)
/7