Section 3

Receiving and Installation

Receiving & Inspection
The Series 15P Inverter control is thoroughly tested at the factory and
carefully packaged for shipment. When you receive your control, there are
several things you should do immediately.
1.
Observe the condition of the shipping container and report any damage
immediately to the commercial carrier that delivered your control.
2.
Verify that the control you received is the same as listed on your
purchase order.
3.
If the control is to be stored for several weeks before use, be sure that it
is stored in a location that conforms to published storage specifications.
(Refer to Section 6 of this manual).

Physical Installation

The mounting location is important. The control should be installed in an area
that is protected from direct sunlight, corrosives, harmful gases or liquids,
dust, metallic particles and vibration. Exposure to these elements can reduce
the operating life and degrade performance of the control.
Several other factors should be carefully evaluated when selecting a location
for installation:
1.
For effective cooling and maintenance, the control should be mounted
on a smooth, non-flammable vertical surface. Table 3-1 lists the Watts
Loss ratings for enclosure sizing.
2.
Provide at least two inches of clearance on all sides for airflow.
3.
Front access must be provided to allow the control cover to be opened
or removed for service and to allow viewing of the Keypad LEDs.
4.
Altitude derating. Up to 3300 feet (1000 meters), no derating is
required. Above 3300 feet, derate peak or continuous output current by
2% for each 1000 feet above 3300 feet.
5.
Temperature derating. Up to 40°C, no derating is required. Above
40°C, derate peak or continuous output current by 2% per °C above
40°C.
Maximum ambient is 55°C.
115VAC
2.5kHz
7.5kHz
PWM
PWM
17 Watts/
20 Watts/
Amp
Amp

Control Installation

The control must be securely fastened to the mounting surface. Use the four
(4) mounting holes to fasten the control to the mounting surface or enclosure.
Shock Mounting
If the control will be subjected to levels of shock greater than 1G or vibration
greater than 0.5G at 10 to 60Hz, the control should be shock mounted.
Excessive vibration within the control can cause internal connections to
loosen and could lead to component failure or electrical shock hazard.
3-1 Receiving and Installation
Table 3-1 Series 15P Watts Loss Ratings
230VAC
2.5kHz
7.5kHz
PWM
PWM
17 Watts/
20 Watts/
Amp
Amp
460VAC
2.5kHz
7.5kHz
PWM
PWM
19 Watts/
28 Watts/
Amp
Amp
MN715P