Specifications And Product Data; Specifications; Operating Conditions - Baldor 15P Series Installation And Operating Manual

Inverter control
Hide thumbs Also See for 15P Series:
Table of Contents

Advertisement

Section 6

Specifications and Product Data

Specifications:

Horsepower
Input Frequency
Output Voltage
Output Current
Output Frequency
Service Factor
Duty
Overload Capacity
Frequency Setting
Frequency Setting
Potentiometer
Rated Storage Temperature:

Operating Conditions:

Voltage Range:
115 VAC Models
230 VAC Models
460 VAC Models
Input Line Impedance:
Ambient Operating
Temperature:
Enclosure:
Humidity:
Altitude:
Shock:
Vibration:
LED Indicators
MN715P
0.33-1HP @ 115VAC
1-5 HP @ 230VAC
1-7.5 HP @ 460VAC
50/60Hz ± 5%
0 to Maximum Input Voltage (RMS)
See Ratings Table
0 to 130Hz
1.0
Continuous
Constant Torque Mode: 200% for 2 seconds
0-10VDC, 4-20mA or the front panel potentiometer
5kW or 10kW, 1/2 Watt
− 30°C to +65°C
90-132 VAC 1f 60/50Hz
180-264 VAC 3f 60Hz/180-230 VAC 3f 50Hz
342-528 VAC 3f 60Hz/342-457 VAC 3f 50Hz
1% Minimum Required
0 to +40°C
Derate Output 2% per °C
over 40°C to 55°C (130°F) Maximum
NEMA 1: ER (suffix) Models
NEMA 1: To 90% RH non-condensing
Sea level to 3300 feet (1000 meters)
Derate 2% per 1000 feet (303 meters) above 3300 feet
1G
0.5G at 10Hz to 60Hz
Power
Fault
Forward run command
Reverse run command
Stop command
150% for 60 seconds
Specifications and Product Data 6-1

Advertisement

Table of Contents
loading

Table of Contents