Baldor 15P Series Installation And Operating Manual page 20

Inverter control
Hide thumbs Also See for 15P Series:
Table of Contents

Advertisement

S1 Settings Continued
Switch
Setting
OFF
1
1
ON
OFF
2
2
ON
OFF
3
3
ON
OFF
ON
4
OFF
5
5
ON
OFF
6
6
ON
OFF
7
7
ON
OFF
8
8
ON
Note 1: If power up start is ON and local commands are used, the drive will resume
operation in the same FWD or REV direction when power is applied.
Note 2: If power up start is ON and remote 2 wire commands are used, the drive will
resume operation if the forward or reverse switch is still closed (2 wire).
Note 3: If power up start is ON and remote 3 wire commands are used, the drive will
not allow power up start operation (unless the momentary contacts stop and
forward or reverse are manually held closed during power up).
Note 4: After power down, if any S1 switch position is changed, power up start is
cancelled.
4-3 Setup and Operation
Description
Base Frequency = 60Hz
Base Frequency = 50Hz
Maximum frequency limit = Base Frequency (60/50Hz)
Maximum frequency limit = 2 X Base Frequency (130 or 110 Hz)
Reverse motor rotation ENABLED
Does not allow reverse motor rotation
Power up Start DISABLED (see notes)
Power up Start ENABLED the control will resume operation as soon
as power is applied. Power up start is disabled the first time you
power up the drive (see notes).
Terminal 2 wire mode (If S1-8 = ON)
Terminal 3 wire mode (If S1-8 = ON)
Analog input VOLTAGE (if S1-7 = ON)
Analog input CURRENT (if S1-7 = ON)
Use local speed reference (front panel potentiometer)
Use remote speed reference (J4 connector)
Use local commands (front panel FWD, REV, STOP)
Use remote commands (J4 connector)
MN715P