Systemsetup - Briggs & Stratton 71045 Installation Manual

100/150/200 amp automatic transfer switch with service disconnect and ac control module
Table of Contents

Advertisement

Available languages

Available languages

System Setup
You mustperformthe f@owingbeforeoperatingthe system:
• if generator i s installedin an arearegularlysubjected to
temperatures below40% (4°0), sebct a 50 second warm up
time by movingjumperJP2 (C)instalbd on transferswitch
control boardfrom '20' positionto '50' position.
• Setthe DPSWl (A) and DPSW2 (B) dipswitches on the
transferswitchcontrol boardto matchthe kW ratingof the
standbygenerator, a s described in SettingDipswitches.
Setting Dipswitcbes
Dipswitches are usedto adjustcontrolboardoperationbased
on generator c apacity.DPSWland DPSW2 switchesare setto
correspond to total systemkW rating.DipswitchDPSWl (A) has
units of 1,000watts;DipswitchDPSW2 (B) hasunits of
10,000watts.
@
NOTICE Use extreme caution when setting dipswitches or
damage to control board will result........
a pencil or small piece of plastb (_ set the dipswitch.
Use
, NEVERuse a screwdriver or an_ type of metal object to
set dipswitches.
....
NOTICE An FC_8 will occuron standbygeneratorcontrol boardif
dipswitches are not properlyestablished as notedabove.
The"On"positionfor the dipswitches is theswitchnumberON
THE TRANSFER S WITCH CONTROL BOARD, not onthe switch.For
example, for an 18,000wattgenerator, s etDPSW2 dipswitch 10 to
"On"position.SetDPSWldipswitch8 to "On"position.10,000plus
8000equals18,000watts.Set only one switch to "On" position
on DPSWl and DPSW2.
Referto following chart for proper switch selection(s).
7kW
7
0
8
0
9kW
9
0
0
0
11kW*
1
10
12kW.
2
. 10
13kW*
3
10
14kW
4
m
10
15kW
5
10
10
17kW
10
18kW
19kW .................... 9
10
o
2o
0
30
,,_ 50kW
0
'
50
58kW
0
60
* Eor generatorswith a rating that includes500 Watts, round down to
(example:1&5 kW setto 13kW)
NOTICE Air densityis lessat highaltitudes, r esultingin less
available enginepower. S pecifically, enginepowerwill decrease 3.5%
for each1,000feet (300 meters) a bovesealevel a nd 1%for each10 °
F (5.6°0)above77°F(25°0).Generators l ocated in theseconditions
musthavethetransferswitchprogrammed appropriately f or this
powerdecrease.
10
BRIGGSandSTRATTON.COM