Connecting the Alarm Input/Output Cables
Menu settings may be required depending on the connected equipment.
(Refer to [AUX FUNCTION](A page 54).
The default setting has been set to alarm input (IN:ALARM).
Alarm input terminal
Connect the infrared sensor, door sensor, metal sensor, manual switch
sensor and the like.
To prevent noise from entering the internal circuit, supply non-voltage
setting signal to the alarm input signal.
Do not supply voltage.
Using the menu, you can select whether to set to alarm when the
contact is short (MAKE), or when the contact is open (BREAK).
Supply such that the alarm signal stays at a minimum of 200 ms or
more. Otherwise, the alarm signal may not be recognized.
.
Alarm output terminal
Connect to alarm devices such as alarm, indicator, light or buzzer.
The alarm output signal is open collector output and turns ON during
an alarm. (Maximum voltage 16 V, current 30 mA)
This terminal has a polarity. Make sure to connect such that a higher
voltage is output from the + terminal than from the - terminal.
Otherwise, it will result in damages.
.
AUX(IN)
GND
AUX(OUT)
100K
GND
Please use a shielded
*
cable.