Table 10 Ups Specifications - Liebert GXT3-10000T230 User Manual

10kva, 50/60 hz, 230v
Table of Contents

Advertisement

Table 10
UPS specifications (continued)
Specification
Static Switch
Nominal frequency
Frequency tolerance
Voltage tolerance
Out-of-phase switching time (ms) in case of inverter
fault and bypass is out of tolerance
Overload
Overload > 100%
In-phase switching time - direct/conditioned (ms)
Condition/direct
105% to 130%
131% to 150%
151% to 200%
>200% (impact load)
Maximum noise level at 1 meter front-side normal
mode and battery mode
Degree of protection
Physical Characteristics
Dimensions, W x D x H, mm (in)
Color
Weight with integrated batteries, kg (lb)
Battery
Optimum battery temperature, °C (°F)
Power output
Recommended number of cells
End of discharge
Battery type
Battery number
Discharging time
Auto battery missing detection
External Battery Cabinet
Battery type
Battery number, pcs.
Dimensions, W x D x H, mm (in)
Color
Weight with integrated batteries, kg (lb)
Performance EN 62040-3
Dynamic characteristics
Step load response
Load 0% to 100% to 0%
Load 20% to 100% to 20%
Startup Operation
Input AC < 100VAC or greater than 280VAC
Input >176 or less than 276
Load 0% to 100% to 0%
1. Maximum input power (normal V, R full load)
float (kVA) = [Pout (KW) / efficiency] / input_power_factor
Example for the 10kVA: float (kVA) = (7,0 / 0,91) / 0,95 = 8100VA
2. Recharge (kVA) = [(Pout (KW) / efficiency) + Pbattchargerinput] / input_power_factor
Example for the 10kVA: Pbattchargerinput = (2.5*268) / efficiency = (2.5*268) / 0,9 = 744W recharge (kVA) =
[(7,0 (KW) / 0,91) + 744] / 0,95 = 8880VA
3. THDi measure method is applied to EN61000-3-2, 1995
4. In-phase switching time direct / conditioned means time line (bypass) transferring to inverter
5. The expected battery life is defined at 20°C. For every increment of 10°C, above 20°C, the expected life is halved
Value
50/60 Hz auto selection
±3.5 Hz
100V - 280V
No transfer
Audible alarm
4
Zero break
Zero break
1 minute
10 seconds
1 second
At least 5 cycles
50dBA
IP20
300 x 675 x 800 (11.8 x 26.6 x 31.5)
Black
105 (231.5)
15 - 25 (59-77)
8.5kW
120
200VDC
HR 1234W F2 12V / 8.5Ah
20
5 minutes
Yes
1Set / 2Set
HR 1234W F2 12V / 8.5Ah
40 / 80
300 x 675 x 800 (11.8 x 26.6 x 31.5)
Black
162 (357)
VFI - S S - 1 1 1
±5% maximum, returns to static regulation within 200 ms.
±3% maximum, returns to static regulation within 200 ms.
UPS will not start
UPS start enabled
±5% maximum, returns to static regulation within 200 ms.
31
Specifications