Connecting Mains And Load; Figure 6 Input And Output Connections With Single Source, Single-Phase Input Supply; Figure 7 Input And Output Connections With Dual Source, Single-Phase Input Supplies; Figure 8 Input And Output Connections With Single Source, Three-Phase Input Supply - Liebert GXT3-10000T230 User Manual

10kva, 50/60 hz, 230v
Table of Contents

Advertisement

3.7

Connecting Mains and Load

When connect the mains supply to the UPS refer to Figures 6 through 8. Choose the connection
method according to the input supply characteristics. Connections must meet these requirements:
• The installer must provide circuit breaker protection according to local codes. The mains discon-
nect should be within sight of the UPS or have an appropriate lock-out. Maintain service space
around the UPS or use flexible conduit.
• The installer must provide output distribution panels, circuit breaker protection, or emergency
disconnect switches according to local codes. Output circuits must not share a common conduit
with input circuits or any other wiring.
• The utility may be derived from a single-phase or three-phase source.
Figure 6
Input and output connections with single source, single-phase input supply
Mains 1 Input ~
L1
L1
L2
Factory-Supplied Jumper
(W36)
230V Input
Figure 7
Input and output connections with dual source, single-phase input supplies
Mains 1 Input ~
L1
L1
L2
Factory-
230V UPS Input
Supplied
Jumper
(W35)
Figure 8
Input and output connections with single source, three-phase input supply
Mains 1 Input ~
L1
L1
L2
400V Input
Factory-Supplied Jumper (W34)
L3
N
GND
BY
L3
N
GND
BY
L3
N
GND
BY
Mains 2 Input ~
N
GND
Mains 2 Input ~
N
GND
230V Bypass Input
Mains 2 Input ~
N
GND
11
Output ~
Connection
L
N
GND
S1
230V
Output ~
Connection
L
N
GND
S1
230V
Output ~
Connection
L
N
GND
S1
230V
Installation
Parallel
S2
Parallel
S2
Parallel
S2