DIP SWITCHES

Auxiliary dip switch controls are located behind front
panel, through an opening below the control panel.
To access, remove front panel. See Fig. 11.
Dip switches are accessible without opening the
control box. Unit must be powered OFF to
effectively change their status.
Factory settings for dip switches will be in the
DOWN position.
See Table 5 - - Dip Switch
Functions for functions of each dip switch position.
Dipswitch
No,
1
Electric Heat Only
2
Wall Thermostat Enable
3
Fan Continuous Run for Heating
4
Fan Cycle for Cool
UP*UP
68--- 75 _F
5*6
20--- 24 _C
7
Freeze Guard Disable
Electric Heating Only / Emergency Heat (For Heat Pump Units Only)
This setting is typically used for Emergency Heating.
Wall Thermostat Enable
A wired wall thermostat can be connected to the unit. If it is, this dipswitch must be moved to the Wall
Thermostat Enable Position, before the wall thermostat will begin control.
Heat and Cool Fan CON/CYC Dip- -switches
Allows the fan to operate in continuous or cycle modes while the unit is in heating or cooling mode
(continuous or cycle):
CON (Continuous)
Allows fan to run continuously, circulating air even when the temperature setting has been satisfied. This switch helps to
maintain the room temperature closer to the thermostat setting.
CYC (Cycle)
This setting allows the fan to cycle on and off with the compressor or electric heater. The fan stops a short time after
the temperature setting is satisfied.
Setpoint Temperature Limits
Provides a restricted range of temperature control.
Room Freeze Protection
If unit senses a room temperature below 40°F, the fan motor and electric strip heat will turn on and warm
the room to 50_F. The fan stops a short time after the temperature is satisfied.
UP
Down
Fig. 21 –
Dip Switches
Table 5—DIP SWITCH FUNCTIONS
UP
Control Panel Enable
Fan Cycle for Heat
Fan Continuous Run for Cooling
UP*DOWN
DOWN*UP
63--- 80 _F
65--- 78 _F
18--- 28 _C
19--- 26 _C
Freeze Guard Enable
Freeze guard
Setpoint Limit 2
Setpoint Limit 1
Fan CON/CYC for cooling
Fan CON/CYC for heating
Wall Thermostat enable
Electric heat only (for Heat Pumps)
DOWN
Heat Pump
For Heat Pump unit only.
Two configurations (5*6)
combine to select set point
DOWN*DOWN
range.
61--- 86 _F
16--- 30 _C
When set point limit set, dis-
play always shows full
(full range)
range.
12
Dip Switches
Fig. 20 –
Dipswitch Location on Unit
REMARKS
DOWN*DOWN
DEFAULT
DOWN
DOWN
DOWN
DOWN
61--- 86 _F
16--- 30 _C
DOWN