Operating Parameters - Omron CJ Series Operation Manual

Sysmac temperature control units
Hide thumbs Also See for CJ Series:
Table of Contents

Advertisement

Data Exchange with the CPU Unit
DM address
Loop
Word
Bits
Loop 1
Loop 2
Loop 3
Loop 4
2-5-6

Operating Parameters

SYSMAC CJ-series CPU Unit
Allocated DM addresses
D20000 to D20099
D20100 to D20199
D20200 to D20299
Unit 3
D20300 to D20399
D20400 to D20499
Unit 5
D20500 to D20599
D20600 to D20699
D20700 to D20799
D20800 to D20899
Unit 9
D20900 to D20999
D20000 + n × 100 to
Unit n
D20000 + n × 100 + 99
Unit 94
D29400 to D29499
Note
46
Setting
Alarm 1 hysteresis Set each alarm's hysteresis in 4-digit BCD or 16-bit binary, accord-
ing to the Data Format set on the Temperature Control Unit's DIP
Alarm 2 hysteresis
switch.
Alarm 1 hysteresis
The values written here are written to RAM.
Alarm 2 hysteresis
Alarm 1 hysteresis
Alarm 2 hysteresis
Alarm 1 hysteresis
Alarm 2 hysteresis
The starting DM Area word (m) for a Special I/O Unit is:
m = 20000 + (100 × unit number)
The Temperature Control Unit's Operating Parameters are set in the DM
words allocated to the Temperature Control Unit as a Special I/O Unit. Operat-
ing Parameters include the Alarm SVs, Control Periods, Proportional Bands,
Integral Times, and other parameters.
Operating Parameters are exchanged each cycle during the I/O refresh
period. Input data is transferred from the Temperature Control Unit to the CPU
Unit and output data is transferred from the CPU Unit to the Temperature Con-
trol Unit.
Input data is
transferred from the
Temperature Control
Unit to the CPU Unit
and output data is
transferred from the
:
CPU Unit to the
Temperature Control
Unit each cycle during
:
1. Loops 3 and 4 are applicable to Temperature Control Units with four control
loops only. If a Temperature Control Unit with two control loops is being
used, the settings for loops 3 and 4 will not be used and will be ineffective
even if they are set.
2. The Special I/O Unit Area words that are allocated to the Temperature
Control Unit in the DM Area are determined by the setting of the unit num-
ber switch on the front panel of the Unit. Refer to 2-3-3 Unit Number
Switches for details on the method used to set the unit number switch.
3. If two or more Special I/O Units are assigned the same unit number, a
"UNIT No. DPL ERR" error (in the Programming Console) will be generat-
ed (A40113 will turn ON) and the PLC will not operate.
Units
Temperature Control Unit
Operating Parameters
D (m+10)
Output data for loops 1
to
and 2 (output refresh)
D (m+29)
D (m+30)
Input data for loops 1
to
and 2 (input refresh)
D (m+49)
Output data for loops 3
D (m+50)
and 4 (output refresh)
to
D (m+69)
(See note 1.)
Input data for loops 3
D (m+70)
to
and 4 (input refresh)
D (m+89)
(See note 1.)
m = 20000 + (100 x unit number)
Section 2-5

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cj1w-tc seriesSysmac cj series