Figure 16 Installing rack-mount handles

9. Insert the UPS, with inner members attached, into slide rail assemblies by inserting top and
bottom edges of inner members into the top and bottom, curved tracks of front members and
sliding the UPS into rack, as shown in Figure 17.

Figure 17 Insert the UPS

NOTE
Ends of inner members are tapered to allow rear of the UPS to be angled upward before
insertion, if space allows.
The UPS should move smoothly into slide rail assemblies. If not, recheck alignment of front
and rear members from Steps 4 through 6.
Factory-supplied rack handles are not intended to be used to lift the UPS. These are intended
to be used to slide the UPS into and out of the rack.
10. Through the rack mount handles, use M5 screws provided in this kit to secure front of the UPS to
rack EIA rails to prevent the UPS from sliding out of position.
11. If optional Liebert
one side of the UPS or stacked beneath the UPS. The installation procedures are the same as
those of the UPS.
Liebert GXT3 UPS
Insert
Inner Member
®
external battery cabinets are connected to the UPS, they can be placed all on
Rack-Mount Handles, 2 pieces
M4 Screw , 8 pieces
Front Member
16
Installation