Through The Wall - Quadra-Fire CASTILE-CE-MBK Owner's Manual

Castile & santa fe pellet stove
Table of Contents

Advertisement

Castile & Santa Fe CE Pellet Stove
G. Through The Wall
Horizontal termination cap must be a minimum of 152mm
from the wall. Approved for mobile home installations. Must
use 76mm to 102mm "L" or "PL" listed pellet venting or listed
double wall pipe and a Quadra-Fire Outside Air Kit in mobile
homes.
Please note that while the minimum clearance for the
termination cap is 152mm there is the possibility of soot
build-up around the termination area. If this occurs we
suggest to move the termination further away from the
house to prevent it.
Straight Out
51mm
Minimum
152mm
Minimum
From Glass
Figure 30.1
45 Degree
Illustration shows venting going in both directions.
Choose which one is best for your installation.
Wall
Thimble
152mm
Minimum
51mm
Minimum
Figure 30.3
October 24, 2011
NOTICE:
Wall
Thimble
152mm
Minimum
Non-combustible Hearth Pad
152mm
Minimum
51mm
Minimum
We strongly recommend that you DO NOT
DOWNWARD VENT.
The following may occur:
• The appliance will not vent properly
• Smoke spillage in the house
• Excessive sooting
Horizontal
152mm
Termination
Minimum
Cap
From Glass
Illustration shows venting going in both directions.
Choose which one is best for your installation.
Wall
Thimble
152mm
Minimum
7068-112B
CAUTION
51mm
Minimum
152mm
Minimum
Non-combustible Hearth Pad
Figure 30.2
152mm
Minimum
51mm
Minimum
Figure 30.4
R
Wall
Horizontal
Thimble
Termination
Cap
51mm
Minimum
Page 29