Castile & Santa Fe CE Pellet Stove
C. Hearth Pad Requirements
If the current flooring is made from wood, provide
adequate surface protection according to the current
national standards..
K
Figure 22.1
K
Figure 22.2
Recommended Hearth Pad Requirements
Hearth Pad Requirements
K
Sides
L*
Back
M
Front
October 24, 2011
L*
K
M
L*
K
M
Millimeters
50
50
152
Must extend 51mm beyond each side of
pipe (shaded area)
Figure 22.3
Must extend 2 inches (51mm) beyond each
side of pipe (shaded area)
Figure 22.4
Exception for Horizontal Installations:
A non-combustible floor protection extending beneath the
flue pipe is required with horizontal venting or under the top
vent adapter with vertical installation. Figure 22.3 & Figure
22.4.
7068-112B
R