he definitions below describe the controls and functions of
the Generator Control Panel (Figure 4).
1. Main Circuit Breaker—This three-pole, 90A main
breaker is provided to protect the the U,O, and V Output
Terminal Lugs from overload.
2. voltage regulator Control — Allows ±15% manual
adjustment of the generator's output voltage.
3. ammeter Change-over switch — This switch allows
the AC ammeter to indicate the current flowing to the
load connected to any phase of the output terminals,
or to be switched off. This switch does not effect the
generator output in any fashion, it is for current reading
only.
4. Frequency Meter — Indicates the output frequency
in hertz (Hz). Normally 60 Hz.
5. aC ammeter — Indicates the amount of current the
load is drawing from the generator per leg selected by
the ammeter phase-selector switch.
6. aC voltmeter — Indicates the output voltage present
at the U,O, and V Output Terminal Lugs.
page 18 — DCa20spxu2 (wiTh MlT20 series) • operaTion anD parTs Manual — rev. #0 (01/18/13)
2
INCREASE
DECREASE
3
1
V
5
U
W
OFF
6
Figure 4. Generator Control Panel

generatOr cOntrOl panel

4
HZ
A
V
1000
2000
0
3000
RPM
Located behind the generator control panel is the Generator
Control Box. This box contains some of the necessary
electronic components required to make the generator
function.
The Control Box is equipped with the following major
components:
„ Over-Current Relay
„ Automatic Voltage Regulator (AVR)
„ Starter Relay
„ Current Transformer
„ Engine Controller
AUTO
MANUAL
OFF/RESET
LOW OIL PRESSURE
HIGH COOLANT TEMPERATURE
OVERCRANK
OVERSPEED
ENGINE RUNNING
MOOOOO-20001Q