11. Parameters accessible with Function Code 04

Function code 04 provides read access to the read-only input registers. The input registers contain the
signals of the UDA2182.

11.1 Signals

Signals provide a means for the user to remotely read status values within the UDA database. In the
function block model, you can think of them as values connected to the output of function blocks. Since
they are controlled by the function block algorithm, they are read-only. Signals can be either analog
(floating-point) or digital (long) depending on the type of output it is monitoring. They are permanently
connected to the function block outputs. In other words, the user doesn't have to configure the connection
to make the output visible. The output value is always visible.

11.2 Input Registers Map

Table 11-1 describes the input register map for Function Code 04.
Conversion between Address (Hex) Number and Register (Decimal) Number
To convert the address number to the register number, convert the address from hexidecimal to decimal
and add 30,001. Registers are addressed starting at zero: registers 30,001-30,016 are addressed as 0-15. To
convert the register number to the address number, subtract 30,001 from the register and convert to hex.
Address
Register
(hex)
(decimal)
0000
30001
0002
30003
0004
30005
0006
30007
0008
30009
000A
30011
000C
30013
000E
30015
0010
30017
0012
30019
0014
30021
0016
30023
0018
30025
001A
30027
001C
30029
001E
30031
January 09

Table 11-1 Holding Registers Map

Parameter Name
PV 1
PV 2
Temperature 1
Temperature 2
Alarm1
Alarm2
Alarm3
Alarm4
Alarm group 1 output
Alarm group 2 output
Analog monitor 1 output
Analog monitor 2 output
Analog monitor 3 output
Analog monitor 4 output
Logic 1 output
Logic 2 output
UDA2182 Communications User Guide
Parameters accessible with Function Codes 04
Type
Input 1 Process Value
Float
Input 2 Process Value
Float
Float
Input 1 Sensor Temperature
Float
Input 2 Sensor Temperature
Long
0=Inactive; 1=Active
Long
0=Inactive; 1=Active
Long
0=Inactive; 1=Active
Long
0=Inactive; 1=Active
Long
On if any Analog Alarm is active
Long
On if any PID Control Alarm is
active
Long
Long
Long
Long
Long
Long
Notes
31