3.2 UDA Serial Communications Setup

Be sure you have an IP address that allows it to be accessible on the intended Ethernet network. Consult
your IT department or network administrator for allocating IP addresses to the UDAs as required.
You will need to set each UDA's IP address prior to network connection since every UDA is shipped with
the default IP address of 192.168.1.254. Placing multiple UDAs on the same network before they have
been given unique IP addresses will cause problems.
Step
1
On the front panel, select the Communication menu option in the Setup menu.
Inputs
Inputs
Outputs
Outputs
Outputs
Outputs
Outputs
Outputs
Relays
Relays
Relays
Relays
Relays
Relays
Relays
Relays
Alarms
Alarms
Alarms
Alarms
Alarms
Alarms
Alarms
Alarms
Monitors
Monitors
Monitors
Monitors
Monitors
Monitors
Monitors
Monitors
Math
Math
Math
Math
Math
Math
Math
Math
Logic
Logic
Logic
Logic
Logic
Logic
Logic
Logic
Auxiliary
Auxiliary
Auxiliary
Auxiliary
Auxiliary
Auxiliary
Auxiliary
Auxiliary
PID Control
PID Control
PID Control*
PID Control*
PID Control
PID Control*
PID Control
PID Control*
Auto Cycling*
Auto Cycling*
Auto Cycling
Auto Cycling
Auto Cycling
Auto Cycling*
Auto Cycling
Auto Cycling*
Variables
Variables
Communication
Communication
Communication
Communication
Communication
Communication
Maintenance
Maintenance
Maintenance
Maintenance
Maintenance
Maintenance
2
In the Communication menu, select RS485.
COMMUNICATION
COMMUNICATION
IR FrontPanel
IR FrontPanel
Modbus
Modbus
RS485
RS485
Ethernet
Ethernet
You will see the following Parameters:
Port Reset
Address
Baud Rate
3
Set the Address to a unique address on your RS485 link.
Note: An address of 0 sets the UDA to its offline state.
4
Set the Baud Rate to the link's baud rate.
Note: Other link characteristics are fixed to: no parity, 1 stop bit, and eight bit characters
5
Scroll to Port Reset at the top of the menu, and press enter.
Change the value to Enable and press enter to lock the values into the communication card.
January 09
Table 3-4 Setting Up the serial communications
Setup
Setup
Setup
Setup
Setup
Setup
Setup
Setup
UDA2182 Communications User Guide
UDA Communications Setup
Action
9