GE D20MX User Manual page 98

Version 1.20 revision 0
Hide thumbs Also See for D20MX:
Table of Contents

Advertisement

98
Standard Name
IEC 61000-4-6
IEC 60255-22-6
IEC 61850-3: clause 5.7.1.1
IEC 60255-22-1
IEC 61000-4-8
IEC 61000-4-9
IEC 61000-4-12
IEC 61000-4-11
IEC 61000-4-16
IEC 61850-3: clause 5.7.1.3
IEC 61000-4-17
IEC 61000-4-29+
Table 56: Safety publications
Standard Name
Description
IEC 61010-1
Safety requirements for electrical
equipment for measurement, control and
laboratory use - General requirements
IEC 60255-5
Insulation coordination for measuring
relays and protection equipment-
Requirements and tests
Table 57: Environmental standards
Standard Name
Description
IEC 60068-2-1
Cold
IEC 60068-2-2
Dry Heat
IEC 60068-2-6
Vibration (sinusoidal)
IEC 600255-21-2
Shock - Operating Response Test
Shock - Non-Operating Withstand
Test
IEC 600255-21-2
Bump – Non operating test
IEC 60068-2-30
Damp heat, cyclic (12 h + 12 h
cycle)
APPENDIX B: STANDARDS & PROTECTION
Description
Immunity to conducted disturbances,
induced by radio-frequency fields
1 MHz burst immunity test
Power frequency magnetic field
immunity test
Pulse magnetic field immunity test
Ring wave
Voltage dips, short interruptions and
voltage variations immunity tests
Test for immunity to conducted, common
mode disturbances in the frequency
range 0 Hz to 150 kHz
Ripple on DC input power port immunity
test
Voltage dips, short interruptions and
voltage variations on DC input power
port immunity test
This standard only applies when using
high voltage DC as the source (100 V DC
to300 V DC).
GE INFORMATION
Test Specification
150 kHz to 80 MHz: 10Vrms
30Vrms, 300Vrms
Test Specification
Dielectric and Resistance
measurements not applicable
due to design (TVS in circuit)
Test Specification
144 hours powered at - 20 °C
144 hours powered at + 70 °C
A logarithmic sweep from 10 Hz to
150 Hz to 10 Hz at 1 oct/min for 1
sweep cycle in the 3 orthogonal axes.
Acceleration level 1 g
Pulse shape: Half sine Pulse duration:
11 mS
- Operating Response Test:
Acceleration level: 5 g's
- Non-Operating Withstand Test:
Acceleration level: 15 g's
3 pulses per polarity per axis for a total
of 18 pulses
Pulse shape: Half sine Pulse duration:
16 mS Acceleration level: 10 g's
1000 pulses per polarity per axis for a
total of 6000 pulses
D20MX HARDWARE USER'S MANUAL

Advertisement

Table of Contents
loading

Table of Contents